X/R ratio & peak current

The key idea

A fault current cannot jump instantly to its final wave — inductance forbids it. The difference shows up as a DC offset that lifts the first peak far above the normal wave. The X/R ratio decides how slowly that offset dies, and κ turns it into a number.

The idea

An inductive circuit has a rule: current cannot change instantaneously. At the moment a fault strikes, the current is whatever it was — nearly zero — but the network is suddenly demanding a large sine wave.

The circuit reconciles the two by adding a DC offset: a one-sided component that starts exactly where it must for the total current to be continuous, and then decays away. While it lives, the AC wave rides on top of it — and the first crest of that ride is the highest instantaneous current of the entire fault: the peak current ip.

How long the offset lives is set by the impedance make-up at the fault:

  • High X/R (near transformers and generators — mostly reactance): the offset decays slowly, still nearly full-size at the first crest. ip approaches twice the symmetrical peak.
  • Low X/R (far along a resistive feeder): resistance kills the offset within a cycle, and the first peak is barely above normal.

The factor κ packages this: ip = κ · √2 · I″k, with κ running from about 1.0 (pure resistance) toward 2.0 (pure reactance).

Try it

The first peak and the DC offset

κ = 1.75 · ip = 24.7 kA (I″k = 10 kA)

2·√2·I″1·√2·I″-1·√2·I″DC offsetip = 24.7 kAtime (0–100 ms) →
10

Move the slider: higher X/R keeps the DC offset alive longer, and the first peak grows toward twice the symmetrical value.

Why it matters

  • ip is a mechanical number. The forces between conductors scale with current squared — at κ = 1.8 the first peak pushes more than three times as hard as the symmetrical wave would. Busbar bracing and breaker making-duty are rated for exactly this instant.
  • The DC offset also stresses breakers. An offset that has not decayed by contact separation makes the current harder to interrupt — breaker standards account for the DC component at high X/R.
  • X/R comes out of the same study. It is not an extra measurement: the fault calculation that gives I″k gives the X/R at the fault location, and κ with it.
The math, if you want itOptional — the page reads completely without it

For the worst-case switching instant, the fault current is:

the asymmetrical current

i(t) = √2 · I″k · [ sin( ωt − φ ) + sin(φ) · e−ωt·R/X ]

where φ = tan⁻¹(X/R). The second term is the DC offset — the dashed curve in the widget — with time constant X/(ωR). IEC 60909 approximates the resulting first peak with:

the peak factor and the peak

κ = 1.02 + 0.98 · e−3R/X  ·  ip = κ · √2 · I″k

The widget above plots exactly these expressions.

See it in Phasor

Phasor reports X/R and κ at every fault location and computes ip from them — then checks it against each switchgear item's making capacity and each busbar's mechanical rating.