Skip to content

Fault current values

The key idea

A fault does not have one current — it has a current that changes over its first moments. Four standard values capture the moments that matter: I″k at the start, ip at the first peak, Ib when the breaker opens, and Ik once everything settles.

The idea

When a fault lands near generators, the current starts at its largest and decays: the machines' internal fields react over a few cycles and their contribution drops. On top of that, the first cycle carries a DC offset that makes the very first peak the biggest single instant of all.

Because equipment fails in different ways, different moments of this story get their own number:

  • I″k — initial symmetrical current (RMS, at the instant of the fault). The reference value. Thermal withstand checks and protection grading start here.
  • ip — peak current (instantaneous, first half-cycle). What the busbar bracing and breaker making-duty must survive mechanically. Set by I″k and the X/R ratio through the factor κ.
  • Ib — breaking current (RMS, at the breaker's contact separation). What the breaker must actually interrupt. Near generators, the decay means Ib is smaller than I″k — a breaker that opens later has less to break.
  • Ik — steady-state current (RMS, after the transients die). The long-duration value, for anything that must carry the fault for seconds.

Try it

Move the breaker's opening time and watch Ib slide down the decay.

Four values on one fault
10 kA8 kA6 kA4 kA2 kA0100200300400500time after the fault (ms) →I″kip25 kA — first peak, off this RMS scaleIb = 6.4 kAIk
80 ms
  • I″kinitial symmetrical

    10.0 kA

    thermal checks, grading

  • ippeak (instantaneous)

    25 kA

    mechanical forces

  • Ibbreaking at 80 ms

    6.4 kA

    breaker rating

  • Iksteady state

    4.0 kA

    long-duration effects

Near a generator, the fault current is largest in the first cycles and decays as the machine's field reacts. A breaker that opens later has less current to break — that is why Ib depends on the breaker's own operating time.

Why it matters

  • Each rating gets checked against its own value. Comparing a breaker's breaking capacity against ip, or busbar bracing against Ib, is the classic wrong-number-right-units mistake.
  • The decay is a generator phenomenon. Far from machines, on a grid-fed network, the values converge: Ib ≈ I″k ≈ Ik. Near generation they spread apart, and the distinctions earn their keep.
  • Motors join in. Induction motors feed the fault for the first cycles and then quit — raising I″k and ip more than the later values. Leaving them out can pass a switchgear check that should fail.

See it in Phasor

Phasor reports all four values per fault location and fault type, plus the κ and X/R behind ip — and compares each against the matching equipment rating, with the margin.

Related concepts